EQ-350

2
  Transmissores Microprocessados  www.equipe- termopar.com.br Tel.: (11) 4191-1244 - Fax: (11) 4195-1 640 Mod. EQ 350 PROFIBUS ® PA ver. 3.0 FOUNDATION TM  Fieldbus ver. ITK 4.51 Automatic switch between protocols Basic or LAS capability with F.F.  Application Standard signal Function Level Mounting DIN form B sensor head Input Lin. R 0..100 kohm Output Profibu s PA FOUNDAT ION Fieldbus Supply Bus-powered Channels 1 channel Configuration Profibus FOUNDAT ION Fieldbus Features PID controller Customer linearisation  Alarm/control Electrical specifications: Specifications range: -40° C to +85°C Common specifications: Supply voltage... .................................. 9...32 VDC Consumption …….........................…... < 11 mA Isolation Voltage, test / operation..... .... 1.5 kVAC / 50 VAC Signal / noise ratio................................ Min. 60 dB Response time (programmable)…….... 1…60s Updating time………………………….... < 400m s Execution time, P ID controller……….... < 200ms Execution time, analogue input……….. < 50m s Signal dynamics, input ......................... 24 bit Calibration temperature………………... 20…28°C  Accuracy, the gr eater of general and b asic values : General values Input type  Absol ute accuracy Temperature coefficient  All ±0.05% of reading ±0.002% of reading / °C Basic values Input type Basic accuracy Temperature coefficient Pt100 and PT1000 ±0.1°C ±0.002°C / °C Ni100 ±0.15 ±0.002°C / °C Cu10 ±1.3°C ±0.02°C / °C Lin. R. ±0.05W ±0.002W / °C Volt ±10µV ±0.2 µV /°C TC type: E, J, K, L, N, T, U ±0.5°C ±0.010°C / °C TC type: B, R, S, W3, W5 ±1°C ±0.025°C / °C EMC immunity influence ............………….<  ±0.1% of reading Extended EMC immunity: NAMUR NE 21, A criterion, burst………..…< ±1% of reading Vibrat ion ......................................................................... IEC 68-2-6 Test FC Lloyd’s specification no. 1............................................... 4 g / 2...100 Hz Humidity ................................................... ...................... < 95% RH (non-cond.) Dimensions...................................................................... Ø 44 x 20.2 mm Tightness (enclosure / terminal) ..................................... IP68 / IP00 Weight........................ ..................................................... 55 g Electrical specifications, input: RTD and linear resistance input: RTD type Min. value Max. value Norm Pt25…Pt1000 Ni25…NI1000 Cu10…Cu1000 Lin.Resistance Potentiometer -200°C -60°C -50°C 0W 0W +850°C +250°C +200°C 10kW 100kW IEC60751/JIS C 1604 DIN 43760 α = 0.00427 - - Cable resistance per wire........... ................................. .....50 W Sensor current..................................................................nom. 0,2 mA Effect of sensor cable resistance (3- / 4-wire)....... ................................................................< 0.002 W /  W Sensor error detection..... .................................................Yes Short circuit detection................................... ............... .....< 15 W TC / mV input: Type Min. Temperature Max. Temperature Norm B E J K L N R S T U W3 W5 Ext. CJC mV +400°C -100°C -100°C -180°C -100°C -180°C -50°C -50°C -200°C -200°C 0°C 0°C -40°C -800 +1820°C +1000°C +1200°C +1372°C +900°C +1300°C +1760°C +1760°C +400°C +600°C +2300°C +2300°C +135°C +800 IEC584 IEC584 IEC584 IEC584 DIN 43710 IEC584 IEC584 IEC584 IEC584 DIN 43710  ASTM E9 88-90  ASTM E9 88-90 IEC60751 - Cold junction compensation (CJC)…..............................< ±0,5 °C Sensor error detection……….........….…….....................yes Sensor error current: When detecting...... .......................................................Nom. 4µA Else……………………………................................0 µA Short circuit detection……………….............................< 3mV Output: FOUNDATION T M  Fieldbus connection: FOUNDATION TM  Fieldbus version.............................. ITK 4.51 FOUNDATION TM  F. capability.........................................Basic or LAS FOUNDATION TM  F. function blocks............................. ....2 analogue and 1 PID PROFIBUS ®  PA connection: PROFIBUS ®  PA protocol standard............ ......................EN 50170 vol . 2 PROFIBUS ®  PA function blocks......................................2 analo gue PROFIBUS ®  PA address (at delivery)..............................126

description

T

Transcript of EQ-350

  • Transmissores Microprocessados

    www.equipe-termopar.com.br Tel.: (11) 4191-1244 - Fax: (11) 4195-1640

    Mod. EQ 350

    PROFIBUS PA ver. 3.0

    FOUNDATIONTM Fieldbus ver. ITK 4.51

    Automatic switch between protocols

    Basic or LAS capability with F.F.

    Application Standard signal

    Function Level

    Mounting DIN form B sensor head

    Input Lin. R 0..100 kohm

    Output Profibus PA FOUNDATION Fieldbus

    Supply Bus-powered

    Channels 1 channel

    Configuration Profibus FOUNDATION Fieldbus

    Features PID controller Customer linearisation

    Alarm/control Electrical specifications:

    Specifications range: -40 C to +85C Common specifications: Supply voltage..................................... 9...32 VDC Consumption ............................ < 11 mA Isolation Voltage, test / operation......... 1.5 kVAC / 50 VAC Signal / noise ratio................................ Min. 60 dB Response time (programmable).... 160s Updating time.... < 400ms Execution time, PID controller.... < 200ms Execution time, analogue input.. < 50ms Signal dynamics, input ......................... 24 bit Calibration temperature... 2028C Accuracy, the greater of general and basic values:

    General values

    Input type

    Absolute accuracy

    Temperature coefficient

    All 0.05% of reading 0.002% of reading / C

    Basic values

    Input type

    Basic accuracy

    Temperature coefficient

    Pt100 and PT1000 0.1C 0.002C / C Ni100 0.15 0.002C / C Cu10 1.3C 0.02C / C Lin. R. 0.05W 0.002W / C Volt 10V 0.2 V /C TC type: E, J, K, L, N, T, U 0.5C 0.010C / C TC type: B, R, S, W3, W5 1C 0.025C / C

    EMC immunity influence .............< 0.1% of reading Extended EMC immunity:

    NAMUR NE 21, A criterion, burst..< 1% of reading

    Vibration ......................................................................... IEC 68-2-6 Test FC Lloyds specification no. 1............................................... 4 g / 2...100 Hz Humidity ......................................................................... < 95% RH (non-cond.) Dimensions...................................................................... 44 x 20.2 mm Tightness (enclosure / terminal) ..................................... IP68 / IP00 Weight............................................................................. 55 g Electrical specifications, input: RTD and linear resistance input:

    RTD type

    Min. value

    Max. value

    Norm

    Pt25Pt1000 Ni25NI1000 Cu10Cu1000 Lin.Resistance Potentiometer

    -200C -60C -50C

    0W 0W

    +850C +250C +200C 10kW

    100kW

    IEC60751/JIS C 1604 DIN 43760

    a = 0.00427 - -

    Cable resistance per wire.................................................50 W Sensor current..................................................................nom. 0,2 mA Effect of sensor cable resistance (3- / 4-wire).......................................................................< 0.002 W / W Sensor error detection......................................................Yes Short circuit detection.......................................................< 15 W

    TC / mV input:

    Type Min.

    Temperature Max.

    Temperature

    Norm B E J K L N R S T U

    W3 W5

    Ext. CJC mV

    +400C -100C -100C -180C -100C -180C -50C -50C

    -200C -200C

    0C 0C

    -40C -800

    +1820C +1000C +1200C +1372C +900C

    +1300C +1760C +1760C +400C +600C

    +2300C +2300C +135C

    +800

    IEC584 IEC584 IEC584 IEC584

    DIN 43710 IEC584 IEC584 IEC584 IEC584

    DIN 43710 ASTM E988-90 ASTM E988-90

    IEC60751 -

    Cold junction compensation (CJC)..............................< 0,5 C Sensor error detection...............................yes Sensor error current: When detecting.............................................................Nom. 4A Else................................0 A Short circuit detection.............................< 3mV Output: FOUNDATIONTM Fieldbus connection: FOUNDATION TM Fieldbus version.............................. ITK 4.51 FOUNDATION TM F. capability.........................................Basic or LAS FOUNDATION TM F. function blocks.................................2 analogue and 1 PID

    PROFIBUS PA connection: PROFIBUS PA protocol standard..................................EN 50170 vol. 2

    PROFIBUS PA function blocks......................................2 analogue

    PROFIBUS PA address (at delivery)..............................126