Post on 12-Feb-2019
ELETRODUTO DE
AÇO GALVANIZADO
CURVA 90° DEAÇO GALVANIZADO
ELETRODUTO DE
PVC RÍGIDO
ELETRODUTO DE
PVC RÍGIDO
ELETRODUTO DE
PVC RÍGIDO
CAIXA DE EMBUTIR
EM GESSO PARA
TOMADAS ALTAS
CAIXA DE EMBUTIR
EM GESSO PARA
TOMADAS MÉDIASE INTERRUPTORES
CAIXA DE EMBUTIR
EM GESSO PARA
TOMADAS BAIXAS
FORRO
UNIDUT METÁLICO
CORTE ESQUEMÁTICO - INSTALAÇÃO EMBUTIDA
SEM ESCALA
DOS COMPONENTES
ELETROCALHA DE
INFRAESTRUTURA P/
ELÉTRICA OUTELECOMUNICAÇÕES
30
0
11
00
22
00
TOMADAS PARA USO GERALSEM ESCALA
TOMADAS 2P+T 20A 250V
CONFORME NBR 14.136/2002
EM CAIXA DE EMBUTIR EM
PVC 4x4" PARA PAREDE DE
GESSO ACARTONADO
INSTALAÇÃO DOS ELETRODUTOS DE ELÉTRICA/LÓGICADISTÂNCIA MÍNIMA ENTRE CAIXAS - 15cmSEM ESCALA
TOMADAS ELÉTRICAS EMCAIXA DE EMBUTIR EM
PVC 4x4" PARA PAREDE
DE GESSO
ACARTONADO
MÍNIMO15 cm
ELETRODUTO DE PVC
RÍGIDO EMBUTIDOELETRODUTO DE PVC
RÍGIDO EMBUTIDO
TOMADAS DE
CABEAMENTO
ESTRUTURADO EM
CAIXA DE EMBUTIR
EM PVC 4x4" PARA
PAREDE DE GESSO
ACARTONADO
TOMADAS 2P+T 20A 250V
CONFORME NBR 14.136/2002
EM CAIXA DE EMBUTIR EM
PVC 2x4" PARA PAREDE DE
GESSO ACARTONADO
A
A
FIXAÇÃO DE ELETROCALHAFIXAR A CADA 1,20mSEM ESCALA
CORTE A-A
VISTA
MONTANTE ESTRUTURAL DA
LAJE SECA (PERFIL C)
GRAMPO "C" PARA
SUSTENTAÇÃO DAELETROCALHA
TIRANTE ROSCA TOTAL Ø1/4"
ELETROCALHA METÁLICAPERFURADA COM VIROLA DO
TIPO "C" COM TAMPA (VER AS
DIMENSÕES EM PROJETO)
PERFILADO PERFURADO
38x19mm PARA SUSTENTAÇÃODA ELETROCALHA
MONTANTE ESTRUTURAL DA
LAJE SECA (PERFIL C)
GRAMPO "C" PARA
SUSTENTAÇÃO DAELETROCALHA
TIRANTE ROSCA TOTAL Ø1/4"
ELETROCALHA METÁLICA LISACOM VIROLA DO TIPO "C" COM
TAMPA (VER AS DIMENSÕESEM PROJETO) PASSAGEM DOS
CABOS DE
TELECOMUNICAÇÕES
ELETROCALHA METÁLICAPERFURADA COM VIROLA DO
TIPO "C" COM TAMPA (VER AS
DIMENSÕES EM PROJETO)PASSAGEM DOS CABOS DE
ILUMINAÇÃO E TOMADAS
PERFILADO PERFURADO
38x19mm PARA SUSTENTAÇÃODA ELETROCALHA
MÍNIMO 30cm
50
25
0
1200
25
0
DETALHE TÍPICO DE CONEXÃO DOELETRODUTO NA ELETROCALHASEM ESCALA
ELETRODUTO DE
AÇO GALVANIZADOELETROLITICAMENTE
BUCHA E ARRUELA
CONDULETE METÁLICODO TIPO MÚLTIPLO
ELETRODUTO DE
AÇO GALVANIZADOELETROLITICAMENTE
ELETROCALHA
METÁLICAPERFURADA COM
VIROLA DO TIPO "C"
COM TAMPA
PAREDE DA ELETROCALHAELETRODUTO
BUCHAARRUELA
FIXAÇÃO DO ELETRODUTO NO TETOSUPORTAR A CADA 1,20mSEM ESCALA
MONTANTE ESTRUTURAL DA
LAJE SECA (PERFIL C)
GRAMPO "C" PARA
SUSTENTAÇÃO DAELETROCALHA
TIRANTE ROSCA TOTAL Ø1/4"
ABRAÇADEIRA DO TIPO "D"
ELETRODUTO DE AÇOGALVANIZADO
ELETRODUTO DE AÇOGALVANIZADO - PASSAGEM
DOS CIRCUITOS DE
ILUMINAÇÃO E TOMADAS
GRAMPO "C" FIXADO NO MONTANTE
ESTRUTURAL DA LAJE SECA PARA SUPORTE DO
ELETRODUTO (VER DETALHE)
FORRO (TETO)
GRAMPO "C" FIXADO NO MONTANTE
ESTRUTURAL DA LAJE SECA PARA
PASSAGEM DO CABO DE AÇO QUESUSTENTA A LUMINÁRIA
MONTANTE ESTRUTURAL DA
LAJE SECA (PERFIL C)
CABO DE AÇO GALVANIZADO Ø1/8" PARA
SUPORTE DA LUMINÁRIA
LUMINÁRIA EMBUTIDA EMFORRO
CABO TRIPOLAR 0,6/1,0kV 3#1,5mm² EM HEPR90°C (LIVRE DE HALÓGENOS) PARA A LIGAÇÃO
DA LUMINÁRIA
BASE CONECTORA
REATOR ELETRÔNICO DE ALTOFATOR DE POTÊNCIA
PLUGUE PADRÃO BRASILEIRO
CONDULETE EQUIPADO COM
TOMADA PADRÃO BRASILEIROPARA LIGAÇÃO DA LUMINÁRIA
FIXAÇÃO DAS LUMINÁRIAS DE EMBUTIRSEM ESCALA
CONEXÃOELETRODUTO/CAIXA
ATRAVÉS DE CONJUNTODE BUCHA E ARRUELA
CONEXÃOELETRODUTO/CAIXA
ATRAVÉS DECONJUNTO DE BUCHA
E ARRUELA
T
r r
T
F
F
TOMADA 2P+T -10A (REF.:
PIALPLUS DA LEGRAND),
PARA ALIMENTAÇÃO DOPAINEL AUDIOVISUAL PARA
SINALIZAÇÃO DEEMERGÊNCIA. REF.: ALARMEHB, EATON OU EQUIVALENTE.
INTERRUPTOR BIPOLAR SIMPLES, 10A/250V
REF.: PIALPLUS DA LEGRAND.
PARA ACIONAMENTO DA SINALIZAÇÃO DEEMERGÊNCIA DOS BANHEIROS DO TIPO
ACESSÍVEIS (PNE)
CAIXA DE SOBREPOR
(MÍNIMO DE 105mmX105mm)COM SIRENE DE
SINALIZAÇÃO INTERMITENTEE STROBE LIGHT, FONTE
INTERNA DE 220Vca-12Vcc.
FORNECIMENTO COMPLETO
ALARME
PNE
SEM ESCALA
DETALHE ESQUEMÁTICO DE SINALIZAÇÃO PARABANHEIROS DO TIPO ACESSÍVEIS (PNE)
F
F rr
CAIXAS METÁLICAS DE PASSAGEM DO TIPO CONDULETE - TIPOS C, E, T, TB, L, X e ED, RESPECTIVAMENTE.
ELETROCALHA METÁLICA PERFURADA COM VIROLA DO TIPO "C", COM TAMPA. (DIMENSÕES: 150x100mm).
ELETRODUTO LEVE EM AÇO GALVANIZADO ELETROLITICAMENTE, DO TIPO LEVE, INSTALAÇÃO APARENTE NOENTREFORRO, Ø3/4" OU CONFORME INDICAÇÃO EM PLANTA.
ELETRODUTO EM PVC RÍGIDO EMBUTIDO NO TETO, PAREDE OU NO PISO, Ø3/4" OU CONFORME INDICAÇÃO EMPLANTA.
CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE (OU CONFORME INDICAÇÃO) INSTALADA A 30cm DO PISOACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:
SÍMBOLO DESCRIÇÃO
QUADRO ELÉTRICO PARA DISTRIBUIÇÃO DE CIRCUITOS (QDC), METÁLICO, DE SOBREPOR, COM FLANGE PARAELETROCALHA.
CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE (OU CONFORME INDICAÇÃO) INSTALADA A 220cm DO PISOACABADO (OU CONFORME INDICAÇÃO) - CAIXA DE PASSAGEM DE CABOS.
BOTOEIRA SIMPLES PARA ACIONAMENTO DE SISTEMA DE ALARME PPNE, FORNECIDO COM TAMPA, A 30cm DO PISO
ACABADO, 10A/250V.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE,INSTALADA A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE,INSTALADAS A 30,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
DUAS TOMADAS 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE,INSTALADAS A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE,INSTALADA A 110,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE,INSTALADA A 220,0cm DO PISOACABADO (REF.: SILENTOQUE, DA LEGRAND), 100VA OU COMO INDICADO.
TOMADA 2P+T PADRÃO BRASILEIRO 250V/20A EM CAIXA DE EMBUTIR 2x4" INSTALADA DIRETAMENTE NO FORRO DO
TETO ACABADO (REF.: PIALPLUS, DA LEGRAND), TENSÃO DE 127V - POTÊNCIA 100VA OU CONFORME INDICAÇÃO.
CAIXA DE DERIVAÇÃO PARA ELETRODUTOS COM LUVA ROSQUEADA EM PVC 2". (DIM.: 100X100X50mm) REF.: MEGA
UMA TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA DE EMBUTIR2x4" EM PVC EMBUTIDA NA PAREDE A 15cm ACIMA DA PORTA DOS BANHEIROS PPNE (REF.: SILENTOQUE DA
LEGRAND), POTÊNCIA 50W, PARA O SISTEMA DE SINALIZAÇÃO DE EMERGÊNCIA PPNE.
TOMADA ALTA 2P+T PADRÃO BRASILEIRO 250V/20A CONFORME NBR 14.136. INSTALADA EM CAIXA DE EMBUTIR 2x4"EM PVC EMBUTIDA NA PAREDE, INSTALADA A 250,0cm DO PISO ACABADO OU CONFORME INDICAÇÃO (REF.:
SILENTOQUE DA LEGRAND). POTÊNCIA 25VA, PARA ATENDIMENTO AO BLOCO AUTÔNOMO.
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DEGESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EMPINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIO
ANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVADE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-32W, DA ITAIM(FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DEDISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DEGESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO EM CHAPA DE AÇO TRATADA COM ACABAMENTO EMPINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. REFLETOR E ALETAS PARABÓLICAS EM ALUMÍNIOANODIZADO DE ALTO BRILHO. EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVADE SEGURANÇA E PROTEÇÃO CONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2001 2xT26-16W, DA ITAIM
(FORNECIDA COMPLETA, COM 2 LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DEDISTORÇÃO HARMÔNICA (THD) MENOR QUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 32W, APROPRIADA PARA FORRO DEGESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COMACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO.EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃOCONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-32W, DA ITAIM (FORNECIDA COMPLETA, COM 2
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENORQUE 10%).
LUMINÁRIA DE EMBUTIR PARA 2 LÂMPADAS FLUORESCENTES TUBULARES DE 16W, APROPRIADA PARA FORRO DEGESSO OU MODULADO COM PERFIL "T" DE ABA 25mm. CORPO / REFLETOR EM CHAPA DE AÇO TRATADA COM
ACABAMENTO EM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM ACRÍLICO LEITOSO.EQUIPADA COM PORTA-LÂMPADA ANTIVIBRATÓRIO EM POLICARBONATO, COM TRAVA DE SEGURANÇA E PROTEÇÃOCONTRA AQUECIMENTO NOS CONTATOS. REF.: MOD.: 2109 2xT16-16W, DA ITAIM (FORNECIDA COMPLETA, COM 2
LÂMPADAS T5 E REATOR ELETRÔNICO (AFP/PARTIDA RÁPIDA) COM TAXA DE DISTORÇÃO HARMÔNICA (THD) MENORQUE 10%).
LUMINÁRIA RETANGULAR DE SOBREPOR TIPO ARANDELA PARA 1 LÂMPADA FLUORESCENTE COMPACTA DE 23W.INSTALADA A 220cm DO PISO ACABADO OU CONFORME INDICAÇÃO EM PLANTA. CORPO EM CHAPA DE AÇO
TRATADA COM PINTURA ELETROSTÁTICA EPÓXI-PÓ NA COR BRANCA. DIFUSOR EM VIDRO PLANO TEMPERADOJATEADO. REF.: MOD.: OLIVINO 1xTC-TSE-23W DA ITAIM, FORNECIDA COM 1 LÂMPADA FLUORESCENTE COMPACTADE 23W-220V.
CAIXA DE LIGAÇÃO OU PASSAGEM REDONDA PARA UTILIZAÇÃO EM ÁREA COBERTA APARENTE. REF.: DAILETMÚLTIPLO REDONDA DA DAISA.
DOIS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE.
ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
SÍMBOLO
UM INTERRUPTOR BIPOLAR SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE. ALTURA
110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
TRÊS INTERRUPTORES BIPOLARES SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA PAREDE.ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
DOIS INTERRUPTORES BIPOLARES PARALELOS, 10A/250V EM CAIXA DE EMBUTIR 4x4" EM PVC EMBUTIDA NA
PAREDE. ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
UM INTERRUPTOR BIPOLAR PARALELO, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE.
ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
UM INTERRUPTOR INTERMEDIÁRIO SIMPLES, 10A/250V EM CAIXA DE EMBUTIR 2x4" EM PVC EMBUTIDA NA PAREDE.ALTURA 110cm DO PISO ACABADO. REF.: SILENTOQUE DA LEGRAND.
PERCURSO DE CABOS QUE SOBE, QUE PASSA E QUE DESCE EM NÍVEL. INDICAÇÃO EM PLANTA.
CAIXA DE PASSAGEM 15x15cm (OU CONFORME INDICAÇÃO) COM TAMPA REVERSÍVEL. CONSTRUÍDA EM LIGA DEALUMÍNIO SILÍCIO, FUNDIDA EM MOLDE PERMANENTE, DE BOM ACABAMENTO, ALTA RESISTÊNCIA MECÂNICA E ÀPROVA CORROSÃO. TAMPA LISA FIXADA POR PARAFUSOS DE AÇO GALVANIZADO, DOTADAS DE JUNTA DEVEDAÇÃO. INSTALADA A 30cm DO PISO ACABADO OU CONFORME INDICAÇÃO. REF.: CP-1515-10 DA WETZEL.
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70°C750V OU CONFORME INDICAÇÃO EM PLANTA. CLASSE 5 DE ENCORDOAMENTO - NEUTRO, FASE, RETORNO SIMPLES,RETORNO PARALELO E TERRA, RESPECTIVAMENTE - #2,5mm² OU CONFORME INDICAÇÃO EM PLANTA.
SIMBOLOGIA - ILUMINAÇÃO E TOMADAS:
1 - MEDIDAS EM MILÍMETROS, EXCETO ONDE INDICADO.
2 - CONSIDERAR AS COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.
3 - AS ELEVAÇÕES INDICADAS TÊM COMO REFERÊNCIA O PISO ACABADO.
4 - AS TOMADAS INDICADAS EM 220V DEVERÃO SER VERMELHAS DE FÁBRICA, DIFERENTEMENTE DAS TOMADASCONVENCIONAIS 127V, E ALÉM DISSO DEVERÃO RECEBER MARCAÇÃO INDELÉVEL COM OS DIZERES "220V", CONFORMEDETALHE APRESENTADO NESTE PROJETO.
5 - TODOS OS CABOS TERMINAIS SERÃO DO TIPO CLASSE 5 DE ENCORDOAMENTO E TERÃO ISOLAMENTO EM DUPLA CAMADA
POLIOLEFÍNICO NÃO HALOGENADO 70°C 750V EXCETO EM LOCAIS SUJEITO À UMIDADE, COMO TUBULAÇÕES ENTERRADASNO SOLO, QUE DEVERÃO SER DO TIPO 0,6/1kV.
6 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CIRCUITOS) EM TODAS AS CAIXAS, CAIXAS DEPASSAGEM E/OU CONDULETES.
7 - TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA INSTALAÇÃO, DEVEM GARANTIR
CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE E PROTEÇÃO MECÂNICA.
8 - EM TODAS AS DERIVAÇÕES UTILIZAR CAIXA DE PASSAGEM DO TIPO CONDULETE METÁLICO MÚLTIPLO.
9 - OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS CURVAS, EVITANDO-SE
TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
10 - NAS INTERLIGAÇÕES DOS ELETRODUTOS METÁLICOS COM AS ELETROCALHAS, UTILIZAR BUCHA E ARRUELA.
11 - SONDAR OS ELETRODUTOS COM CABO DE NYLON, DEIXANDO UMA SOBRA DE ± 1,0m EM CADA CAIXA PARA A PASSAGEMDE CABOS.
12 - TODOS OS ELETRODUTOS EM PVC DEVERÃO OBEDECER À NBR 15.465. NÃO SERÃO ACEITOS PRODUTOS IDENTIFICADOSCOMO "MANGUEIRAS".
13 - NOS TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO,ENTREFORRO OU ENTREPISO) DEVERÃO SER UTILIZADOS ELETRODUTOS LEVES DE AÇO GALVANIZADO ELETROLITICAMENTECONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO. PARA INSTALAÇÕESEXTERNAS, UTILIZAR ELETRODUTOS DE AÇO GALVANIZADO A FOGO DO TIPO PESADO CONFORME NBR 5.624.
14 - ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO (INCLUSIVE LUMINÁRIAS) ATRAVÉS DO
CABO DE PROTEÇÃO Pe (CABO VERDE DOS CIRCUITOS, TERRA) MAIS PRÓXIMO.
15 - UM MESMO CABO DE PROTEÇÃO (TERRA) PODERÁ SER COMUM A VÁRIOS CIRCUITOS, DESDE QUE SUA BITOLA SEJAIDÊNTICA AO CABO FASE DE MAIOR SEÇÃO CONTIDO EM UM CONDUTO/NICHO DE ELETROCALHA.
16 - ONDE EXISTIR FORRO E/OU PISO ELEVADO, AS ELETROCALHAS DE PASSAGEM DOS CABOS ELÉTRICOS DEVERÃO SERINSTALADAS SOBRE O FORRO OU ABAIXO DO PISO ELEVADO. ESTAS DEVERÃO SER DE USO EXCLUSIVO PARA OS SISTEMAELÉTRICO E DEVERÃO ESTAR DISTANTES PELO MENOS 30cm DAS ELETROCALHAS QUE CONTENHAM CABOS DETELECOMUNICAÇÕES.
17 - UTILIZAR O SEGUINTE CÓDIGO DE CORES PARA CABOS: FASE: PRETO - NEUTRO: AZUL CLARO - TERRA: VERDE - RETORNO: BRANCO - RETORNO PARALELO: CINZA.
18 - EM SITUAÇÕES ONDE A VIGA ESTRUTURAL TORNAR INVIÁVEL A PASSAGEM DOS CONDUTOS ELÉTRICOS, A INSTALAÇÃO
DEVERÁ SER FEITA ABAIXO DA VIGA PARA TRANSPOSIÇÃO DESTES OBSTÁCULOS UTILIZANDO-SE TIRANTES PARA EXTENSÃODOS SUPORTES (VER DETALHES), PODENDO TAMBÉM UTILIZAR ELETRODUTOS METÁLICOS FLEXÍVEIS (SEALTUBE).
19 - TODO E QUALQUER PONTO DE CABEAMENTO ESTRUTURADO DEVERÁ SER ACOMPANHADO DE SEU RESPECTIVO PONTOELÉTRICO, CONFORME INSTALAÇÕES DE CABEAMENTO (VER PROJETO ESPECÍFICO). PARA INSTALAÇÕES EMBUTIDAS,
PREVER DISTÂNCIA MÍNIMA DE 15cm ENTRE AS CAIXAS DE ELÉTRICA E DE CABEAMENTO PARA ATENDER A UM MESMOEQUIPAMENTO.
20 - TODAS AS LUMINÁRIAS, POR SEGURANÇA, DEVERÃO SER FIXADAS ATRAVÉS DE CABO DE AÇO AOS MONTANTESESTRUTURAIS DA LAJE (VER DETALHE)..
21 - OS ALIMENTADORES DO QDC A PARTIR DO PADRÃO DE ENTRADA (INCLUINDO O PADRÃO DE ENTRADA DE ENERGIAJUNTO À CONCESSIONÁRIA) DEVERÃO SER OBJETO DE PROJETO ESPECÍFICO.
22 - OS CHUVEIROS ELÉTRICOS DEVERÃO TER RESISTÊNCIA DO TIPO BLINDADA OU SER APROPRIADOS PARA INSTALAÇÕESEM CIRCUITOS PROTEGIDOS ATRAVÉS DE IDR (INTERRUPTOR DIFERENCIAL RESIDUAL) PARA EVITAR DESLIGAMENTOSINDEVIDOS.
23 - TODOS OS BANHEIROS DO TIPO ACESSÍVEIS (PNE) DEVERÃO POSSUIR SINALIZAÇÃO DE EMERGÊNCIA DE ACORDO COM ANBR-9050. PARA ESQUEMÁTICO DE FUNCIONAMENTO DO SISTEMA, VER DETALHE ESPECÍFICO NESTE PROJETO.
24 - PROJETO ELABORADO DE ACORDO COM AS ESPECIFICAÇÕES DA NBR-5410:2004, SEGUINDO AS NECESSIDADESAPONTADAS PELO LAYOUT SUGERIDO PELO CLIENTE. QUALQUER ALTERAÇÃO DEVERÁ SER COMUNICADA AO PROJETISTAPARA VERIFICAÇÃO.
25 - O MEMORIAL DESCRITIVO E QUANTITATIVO FAZEM PARTES INTEGRANTES DESTE PROJETO, E DEVERÃO SERCONSULTADOS ANTES DE QUAISQUER ORÇAMENTOS OU INSTALAÇÕES.
NOTAS GERAIS:
1 - SISTEMA EM BAIXA TENSÃO TRIFÁSICO 220/127V - 60Hz - Icc MÍNIMO DE 5,0kA.
2 - A ILUMINÂNCIA MÉDIA DOS AMBIENTES DA EDIFICAÇÃO FORAM DETERMINADAS CONFORME RECOMENDADOPELA NBR-5413:1992.
3 - ESQUEMA DE ATERRAMENTO ADOTADO: TN-S.
4 - EM RELAÇÃO AS PRESCRIÇÕES DE PROTEÇÃO CONTRA INCÊNDIO, A EDIFICAÇÃO FOI CLASSIFICADA COMOBD-3 (TUMULTUADA).
5 - TEMPERATURAS CONSIDERADAS EM PROJETO:
- TEMPERATURA AMBIENTE: 30°C; - TEMPERATURA NO SOLO: 20°C.
6 - LIMITE MÁXIMO DE QUEDA DE TENSÃO ADMITIDA: - 7% CALCULADO A PARTIR DOS TERMINAIS SECUNDÁRIOS DO TRANSFORMADOR MT/BT ATÉ O PONTO DEUTILIZAÇÃO.
7 - NORMAS APLICÁVEIS:
- ELETRODUTOS DE AÇO GALVANIZADO ELETROLÍTICO: ABNT NBR 13.057; - ELETRODUTOS DE PVC RÍGIDO: ABNT NBR 15.465; - CONDUTORES DE COBRE 70°C 750V OU 0,6/1kV, NÃO-PROPAGANTES DE CHAMA, LIVRES DE HALOGÊNIO E
COM BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS: ABNT NBR 13.248; - INTERRUPTORES PARA INSTALAÇÕES ELÉTRICAS FIXAS DOMÉSTICAS E ANÁLOGAS: ABNT NBR NM 60.669-1; - PLUGUES E TOMADAS PARA USO DOMÉSTICO E ANÁLOGO ATÉ 20A/250V EM CORRENTE ALTERNADA: ABNTNBR 14.136;
- DISJUNTORES TERMINAIS ATÉ 125A (MINI-DISJUNTORES): ABNT NBR IEC 60.947-2; - DISJUNTORES ACIMA DE 125A (CAIXA MOLDADA): ABNT NBR IEC 60.947-2;
- DISJUNTORES PADRÃO CEMIG: NEMA (CONFORME HOMOLOGAÇÃO); - DISPOSITIVOS DIFERENCIAL RESIDUAL (DR): ABNT NBR NM 61.008;
- DISPOSITIVOS PROTETORES DE SURTOS (DPS): NBR IEC 61.643-1;
- DUTOS CORRUGADOS DE POLIETILENO (PE) PARA INFRAESTRUTURAS DE ENERGIA E TELECOMUNICAÇÕES(PEAD): ABNT NBR 15.715;
- CONTATORES MODULARES PARA ILUMINAÇÃO: IEC 61.095; - BLOCOS AUTÔNOMOS PARA ILUMINAÇÃO DE EMERGÊNCIA: ABNT NBR 10.898;
- QUADROS ELÉTRICOS: ABNT NBR IEC 60.439-1.
PARÂMETROS GERAIS DE PROJETO:
ELETRODUTOS PVC/AÇO
e
mm
e
mm
2,3
2,7
2,9
3,0
3,1
3,8
4,0
5,0
DIÂMETRO
NOMINAL-DN
mm POL
EXTERNO-DE
mm
DIÂMETRO
NOMINAL-DN
mm
25
32
40
50
60
75
85
110
POL
3/4
1
1.1/4
1.1/2
2
2.1/2
3
4
EXTERNO-DE
mm
25,9
33,0
42,0
47,4
59,0
74,7
87,6
113,1
ELETRODUTOS DE AÇO CARBONO, TIPO LEVE I, CONF. NBR 13057
ESPESSURA NOMINAL DA PAREDE
ELETRODUTOS DE PVC RÍGIDO ROSQUEÁVEL, CLASSE B, CONF. NBR 6150
ESPESSURA NOMINAL DA PAREDE
1,5
1,5
2,0
2,25
2,25
2,85
2,65
2,65
20
25
32
40
50
65
80
100
3/4
1
1.1/4
1.1/2
2
2.1/2
3
4
25,2
31,5
40,5
46,6
58,4
74,1
86,8
111,6
FORMATO INTERNACIONAL A1 ALONGADO (1026 x 594mm)
abrasip-mg
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDESUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDEPROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO
FOLHA:
01
05
ETAPA:
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVODETALHES CONSTRUTIVOS, NOTAS
GERAIS E SIMBOLOGIA
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL VIABILE00 27/09/2012
DATAOBJETOREVISÃO
DATA:
NOME DO ARQUIVO CAD:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA OUTUBRO/2013
UNIDADE:ESCALA:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R07-ELE-01-PE-T1T.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
TIPO T1T - TÉRREA
REVISÃO DA ARQUITETURA VIABILE01 18/10/2012
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE02 29/10/2012
SUBSECRETARIA DE INOVAÇÃO E LOGISTICASUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
Secretaria de Estado de Saúde de Minas Gerais
Cidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -
Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
EMISSÃO FINAL VIABILE03 08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE04 01/02/2013
REVISÃO DETALHAMENTO VIABILE05 26/09/2013
REVISÃO DETALHAMENTO VIABILE06 14/10/2013
ALTERAÇÃO PARA INSTALAÇÕES EMBUTIDAS VIABILE07 31/10/2013
AUTOCLAVE
CALÇADA
RUA
L1aa
2x16W
L1aa
L1ab
2x16W
L1ac
2x32W
L1ac
L1ad
2x32W
L1ad
2x32W
L1ae
2x32W
L1ae
2x32W
L1af
2x32W L1af
2x32W
L1af
L1ag
2x32W
L1ag
2x32W
L1ag
L1ah
2x32W
L1ah
2x32W
L1ah
L1aj
2x32W
L1ai
2x32W
L1ai
2x32W
L1aj
2x32W
L1ai
2x32W
L1ai
2x32WL1ai,aj
L2ak
2x16W L2ak
L2al
2x16WL2al
L2am
2x32W L2am
2x32W
L2am
2x32W
L2an
2x32W
L2ao
2x32W
L2an,ao
L2ap
2x32W
L2ap
L2aq
2x32W
L2aq
2x32W
L2aq
2x32W
L2aq
L2ar
2x16W
L2ar
L2at
2x32W
L2at
2x32WL2at
L2au
2x32W
L2au
2x32W
L2au
L2av
2x32W
L2av
L2ax
2x16W
L2ax
L2ay
L2aw
L3bb
2x32W
L3bb
2x32W
L3bb
2x16W
L3be
2x32W
L3be
2x32W
L3be
L3bf
2x32WL3bg
2x32WL3bg
L3bh
2x32W
L3bh
L3bi
2x32W
L3bj
2x32W
L3bj
L4bk
2x16W
L4bk
2x16W
L4bk
2x16W
L4bl
2x16W L4bl
2x16W
L4bl
2x16W
L4bm
2x16W
L4bm
2x16W
L4bm
2x16W
L4bm
L4bmL4blL4bl
L4bm
L4bk
L4bn
2x32W
L4bn
2x32W
L4bn
2x32W
L4bn
2x32W
L4bo
2x32W
L4bo
2x32W
L4bo
2x32W
L4bo
2x32W
L4bn,bo
COPA
COLETA
TRIAGEM
APOIO
AGENTES
ENDEMIAS
AGENTES
DE SAÚDE
ESTERILIZAÇÃO
GINECOLOGIA
DEPOSITO
CIRCULAÇÃO
PR
OJE
ÇÃ
OC
AIX
A D
'AG
UA
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
L4bk
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0#4,0
#4,0
#4,0
#4,0
L5ad
L5aa
L5aa
L5aa
L5aa
L5aa
L5ab
L5ab
L5ab
L5ab
#4,0
A B
B
B C
D
D
D
VER NOTA 5
VER NOTA 5A
LEGENDA PARA PERCURSO DE CABOS (QDC-T1/T):
B
C
D
#4,0
#4,0
#4,0
#4,0
FOLHA:
02
05
ETAPA:
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVOPLANTA DE ILUMINAÇÃO
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL VIABILE00 27/09/2012
DATAOBJETOREVISÃO
DATA:
NOME DO ARQUIVO CAD:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
UNIDADE:ESCALA:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R06-ELE-02-PE-T1T.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDESUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDEPROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1T - TÉRREA
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
REVISÃO DA ARQUITETURA VIABILE01 18/10/2012
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE02 29/10/2012
SUBSECRETARIA DE INOVAÇÃO E LOGISTICASUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
Secretaria de Estado de Saúde de Minas GeraisCidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
EMISSÃO FINAL VIABILE03 08/11/2012
04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE31/01/2013
ESCALA: ..................................................... 1/75
PLANTA DE ILUMINAÇÃO
05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS VIABILE03/09/2013
5-OS ELETRODUTOS PARA ALIMENTAÇÃO DAS ARANDELAS EXTERNAS DEVERÃO SER INSTALADOS SOBRE AS JANELAS,A 2,70m DO PISO ACABADO.
06 EMISSÃO FINAL VIABILE14/10/2013
12-1,8kVA
1,8kVA
T4-200VA
T5-2x200VA
T2-2x200VA
2x200VA
21-2
00V
A
2x200VA
T20-2x200VA
600VA
2x200VA
2x200VA
T5-200VA
T7-2x200VA
T14-200VA
6500W
6500W
600VA
T18-600VA
1kVA
600VA
600VA
T1
T1
T1
T1
T1 T1
T1
T1T19
T2T2
T19
T3
T1 T1
T1
T1
T1 T1
T3
T4
T4
#4,0T4
#4,0
T4
#4,0
T4
#4,0
T19
T3
T19 T4
#4,0
T3
T19 T4
#4,0
T3
T19 T4
#4,0
T3
T19
T1
T5
T5
T5
T5
#4,0
T29
T5
#4,0
T29
T5
#4,0
T5
#4,0
T5
#4,0
T5
#4,0
T6
T6
T6
T6
T6
T7
T7
T7
T6 T7
T6 T7
T6T6T32
T7T6
T8
T8T37-1,11kW-220VT31-1,11kW-220V
T32-1,11kW-220V
T29-1,11kW-220V
T8 T8
T8
T37
T37
T8
T8
T10
T10
T9
T11
T9
T9
T9
T9
T12T10 T11
#6,0
T10T10
T10 T12
#6,0
T11
T12T10
#6,0
T10
T13b'
T13b'
T13a'T13a'
T13
T13
T13
T13
T13
T13
T13
#4,0
T13
#4,0
T9
T7
T13
#4,0
T7
T15 T15
T15
T15
T15
T15
T35-1,11kW-220V
T36-1,11kW-220V
T15
T15T15
T35
T13T15
#4,0
T15
T15
T13T15
#4,0
T13T15
#4,0
T13T15
#4,0
T36
T13T15
#4,0
T13
#4,0
T36
T14
T38-1,11kW-220V
T14
T20
T20
T20
T20
T21
T21
T20
T20
T21 T21T21
T21T21
T40-1,11kW-220V
#4,0
T21T20
T21
#4,0
T20T13
T21
#4,0
T20T13
T13
#4,0
T20
T39-1,11kW-220V
T17
T17 T17
T17
T17
T14
T39T38
T14 T16
T20
T22T22
T22
T22
T22
T22T22
T22
T22
T22
T22
T22
T22
T22
T43-1,11kW-220V
T42-1,11kW-220V
T22
T22
T22
T22
T45
T45T22
T45T22
T45
T23
#4,0
T24
#4,0
T23
T27
T27T27
T27 T27
T27
T27
T26T25
T25
T25 T25 T25
T25
T19
T19
T19
T19 T4
#4,0
T3
T19 T4T3 T13
#4,0
T19 T13
#4,0
T3 T4 T9
A
T19
T19 B
B
C
D
E
F
T28-1,11kW-220V
T31 T32
T30-1,11kW-220V
T30
#4,0
#4,0
T30
#4,0
#4,0
#4,0
#4,0
T7
#4,0
T35
#4,0
#4,0
#4,0
#4,0
T14
#4,0
T20
T39T38
#4,0
T44T40
#4,0
T44
#4,0
T30
#4,0
T28
#4,0
T28
#4,0
T43
#4,0
T43
#4,0
T42T43
#4,0
T42
T1 T13
#4,0
T3 T4 T9T19
T33 T13T1 T3 T9T19 T28
#4,0
T1 T13T2 T3 T9T33 T28
#4,0
T19
G
H
I
J K L
T18-600VA
M N N N N O P
Q
R
R
S
S
T
T
T27
T27
T25 T26T27
#4,0
T25 T26T22 T13
#4,0
U
T46-1kVAT49
#4,0
T27
T47 T48
#4,0
T41T34
T34-1,11kW-220V
T41-1,11kW-220V
T47-1,11kW-220V
T48-1,11kW-220V
T47 T48
#4,0
T41
T47 T48
#4,0
T48
#4,0
T40
#4,0
T49-1kVAT46T33
T49
#4,0
T46
#4,0
T33 T33
T33T33
T13T13
T4
T4
T33
T33
T33
COPA
COLETA
TRIAGEM
escaninhos
AGENTES
DE SAÚDE
ESTERILIZAÇÃO
GINECOLOGIA
CIRCULAÇÃO PR
OJE
ÇÃ
OC
AIX
A D
'AG
UA
T25
T23
T23
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
T4-200VA
#4,0
#4,0
T19 T4
#4,0
T3
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
T5-200VA
#4,0
#4,0
#4,0
#4,0
#4,0 #4,0
#4,0#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
T14-200VA
#4,0
T14
#4,0
T14
#4,0
T14
#4,0#4,0
#4,0
#4,0
T17
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
21-2
00V
A
#4,0
T21
#4,0
T13
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0
#4,0#4,0
#4,0
#4,0
#4,0
#4,0
T13
T16-1,0kVA-220V
T15
A
LEGENDA PARA PERCURSO DE CABOS (QDC-QDC-T1/T):
B
C
D
E
F
G
I
J
K
L
M
N
O
P
Q
R
S
T3 T13T9
#4,0
T2 T28T1 T11T10 T12
#6,0
T13
#4,0
T28 T12
#6,0
T29
T3 T13T9 T4T2 T28T1 T11T10 T12
#6,0
T29T5T6
T3 T13T9 T4T2
#4,0
T28T1 T11T10 T12
#6,0
T29T5T6
T3 T13T9 T4T2
#4,0
T28T1 T11T10 T12
#6,0
T29T5T6 T30 T31 T32
T3 T13T9 T4T2
#4,0
T28T1 T11T10 T12
#6,0
T29T5T6 T30 T31 T32T7
T3 T9T2T1 T10T6 T7
T34T28 T12
#6,0
T29 T30 T31 T32
T3 T9T2T1 T10T6 T7
T34T31 T32 T35 T12
#6,0
T3 T9T2T1 T10T6 T7
T34T31 T32 T35 T12
#6,0
T36
T3 T9T2T1 T11T10T6 T7
T30 T34T31 T32 T35 T12
#6,0
T36
T3 T9T2T1 T11T10T6 T7 T14
T29 T30 T34T31 T32 T35 T36 T38 T39 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14
T16T17 T20 T29 T30 T34T31 T32 T35 T36 T38 T39 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16
T29 T30 T34T31 T32 T35 T36 T38 T39 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16
T17 T18 T20 T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T44 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16T17
T18 T20 T21 T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T44 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16T17T18
T20T21T22 T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T44 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16T17T18T20
T28 T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T44 T12
#6,0
T3 T9T2T1 T11T10T6 T7 T15T14 T16T17T18T20
T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T42 T43 T44 T12
#6,0
TT3 T9T2T1 T11T10T6 T7 T15T14 T16T17T18T20
T28 T29
#4,0
T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T42 T43 T44 T12
#6,0
UT3 T9T2T1 T11T10T6 T7 T15T14 T16T17T18T20
T29 T30 T34T31 T32 T35 T36 T38 T39 T40 T41 T42 T43 T44 T12
#6,0
T46
T46
#4,0
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
T46
#4,0
T28
#4,0
#4,0
T28
#4,0
T28
#4,0
T28
#4,0
T28
#4,0
T28
#4,0
T28
T29
#4,0
T28T15T13 T14
T30T29
#4,0
T28T11
T30T29
#4,0
T28T15T11 T13
#4,0
T15T11 T13
T46
#4,0
T13
T28
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37
T37T26
H
T3 T9T2T1 T6 T7
T34T28 T12
#6,0
T29 T30 T31 T32 T46
#4,0
T13T10 T11 T37 T41 T48T47
T41 T48T47
T41 T48T47
T41 T48T47
T41 T48T47
T41 T48T47
T41 T48T47
T41 T48T47
T48T47
T48T47
T47 T48
T47 T48
T47 T48
T48T47
T48T47
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T49
T33T19 T4
T3 T13T9T2T1 T11T10T33T19 T4 T5
T33T19
T33T8 T19
T33T8 T19
T33T8 T19
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T33T8 T19
#4,0
T45T27T25
T5T4
T45
T45
T45
T21T22
T21T22
T21T22
T13
T13
T13
T4 T5
T4 T5
T4 T5
T13T5T4
T13T5T4
T13T5T4
T17 T18 T20
T13T5T4
T13T5T4
T15 T16 T20
T13T5T4
T5T4
T13 T15
T5T4
T5T4
T5T4
T5T4
FOLHA:
03
05
ETAPA:
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVOPLANTA DE TOMADAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL VIABILE00 27/09/2012
DATAOBJETOREVISÃO
DATA:
NOME DO ARQUIVO CAD:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
UNIDADE:ESCALA:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R06-ELE-03-PE-T1T.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDESUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDEPROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1T - TÉRREA
abrasip-mg
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE02 29/10/2012
REVISÃO DA ARQUITETURA VIABILE01 18/10/2012
SUBSECRETARIA DE INOVAÇÃO E LOGISTICASUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
Secretaria de Estado de Saúde de Minas GeraisCidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
EMISSÃO FINAL VIABILE03 08/11/2012
04 ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE31/01/2013
PLANTA DE TOMADASESCALA: ............................................ 1/75
05 READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS VIABILE03/09/2013
06 EMISSÃO FINAL VIABILE14/10/2013
R
S
TBARRA 2 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
TERRA
Pe R S T N
#10,0
QDC-T1/T - DIAGRAMA MULTIFILAR (96 POLOS)
BARRA 1 - IN MÍNIMO: 150A - TRIFÁSICO - Icc MÍNIMO: 10kA
#10,0
#10,0
#10,0
#10,0
#10,0
#10,0
#10,0
FUSÍVEL MODULAR63A
L1
16A
#4,0
VER PROJETO ESPECÍFICODE ALIMENTADORES/IMPLANTAÇÃO
NE
UT
RO
DR
L2
16A
#4,0
40A (C)
63A (C) 63A (C)
#16,0
NEUTRO
#10,0
#10,0
#16,0
BARRA 3 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
L4
16A
#4,0
R
S
T
R
S
TBARRA 4 - PENTE TRIFÁSICO MÍNIMO 24 PINOS - 80A
DETALHE SUGESTIVO DO QUADRO
QUADRO METÁLICO DE SOBREPOR
INTERRUPTOR
TETRAPOLAR
DR3-In 40A
SENS. 30mA
TIPO AC
R
S
TBARRA 5 - PENTE TRIFÁSICO MÍNIMO 23 PINOS - 80A
T28
16A
#4,0
T29
16A
#4,0
16A
#4,0
16A
T43
16A
#4,0
T1
10
#4,0
T6
16A
#4,0
T7
16A
#4,0
T15 T9
T34
16A
#4,0
T35
16A
#4,0
T10
16A
#4,0
T23
32A
#6,0
63A (C)
#16,0
T2
16A
#4,0
T3
16A
#4,0
T4T5
16A
#4,0
16A
#4,0
16A
#4,0
16A
#4,0
T19
16A
#2,5
T30
16A
#4,0
T32
16A
#4,0
T31
16A
#4,0
T36
16A
#4,0
T42
16A
#4,0
T20
16A
#4,0
T40
#4,0
T41 T44
16A
#4,0
RES.T11
16A
#4,0
T12
16A
#6,0
T13
16A
#4,0
T22
16A
#4,0
T25
16A
#4,0
T24
32A
#6,0
RES. RES.
#10,0
T8
16A
#2,5
L3
16A
#4,0
RES. RES. RES. T14
16A
#4,0
T17
16A
#4,0
T45
16A
#4,0
16A
#4,0
16A
T39
16A
#4,0
T37
#4,0
T38
T18
16A
#4,0
T21
16A
#4,0
T16
16A
#4,0
RES. RES.RES.
T26
16A
#4,0
T27
16A
#4,0
RES.
T46
16A
#4,0
T47
16A
#4,0
T48
16A
#4,0
T49
16A
#4,0
T33
16A
#2,5
RES. RES.
DPS
175V
CLASSE I/II
12,5kA - 10/350us
20kA - 8/20us
DISJUNTOR
GERAL
200A
MÍNIMO DE 10kA
L5
16A
#2,5
01 - TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60.947-2(MINI-DISJUNTORES PADRÃO EUROPEU CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS DECARGAS) E SERÃO DIMENSIONADOS PARA Icc = 5,0kA/220V. OS DISJUNTORES GERAIS FORAM
DIMENSIONADOS PARA Icc >= 10kA/220V E DEVERÃO SER DO TIPO TERMOMAGNÉTICO EM CAIXA MOLDADA .
02 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS ATRAVÉS DE
ETIQUETAS ACRÍLICAS DE IDENTIFICAÇÃO CONFORME NOMES DOS CIRCUITOS CONSTANTES NO QUADRODE CARGAS.
03 - FORAM PREVISTOS ESPAÇOS RESERVAS MÍNIMOS PARA AMPLIAÇÕES FUTURAS, COM BASE NO
NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADO NO QDC E DE ACORDO COM A NBR-5410:2004.
04 - O QUADRO SERÁ METÁLICO, DE SOBREPOR (PREVER ESTRUTURA NO STEEL FRAME PARA
SUSTENTAÇÃO), COM NO MÍNIMO IP-30 (EXCEÇÃO AOS QUADROS LOCALIZADOS AO TEMPO, QUE DEVERÃO
POSSUIR GRAU DE PROTEÇÃO MÍNIMO IP-54), PROVIDO DE ALETAS PARA VENTILAÇÃO, PORTA DE TRINCO
COM CHAVE, NÃO ESTAR INSTALADO EM ÁREAS MOLHADAS OU ÚMIDAS, LONGE DE GÁS, DOTADO DE FÁCIL
ACESSO E NÃO SER OBSTRUÍDO, DEVENDO POSSUIR SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO
NBR IEC 60.439-1 EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
05 - O QUADRO DEVERÁ POSSUIR, ALÉM DOS DISJUNTORES TERMINAIS DESCRITOS NO QUADRO DECARGAS, DISPOSITIVOS DR, DPS DE ENTRADA COM PROTEÇÃO BACKUP, BARRAS DE TERRA E NEUTRO,SENDO AS BARRAS DE NEUTRO PARA DR SEGREGADAS DA BARRA DE NEUTRO GERAL DO QUADRO,
CONFORME LAYOUT SUGESTIVO PRESENTE NO DIAGRAMA MULTIFILAR.
06 - O QUADRO DEVERÁ POSSUIR PLACA DE MONTAGEM INTERNA NA COR LARANJA, CANALETAS PARA A
PASSAGEM DE CABOS (RESPEITANDO A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESTAS CANALETAS,SEGUNDO ORIENTAÇÕES DA NBR-5410), BASE CONECTORA PARA A DISTRIBUIÇÃO DOS CABOS (ENTRADA E
SAÍDA) E IDENTIFICAÇÃO DE NOME, TENSÃO E FREQUÊNCIA EM SUA PORTA, EM ETIQUETA ACRÍLICA DE
FUNDO PRETO E LETRAS BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO
QUADRO, CONFORME DIZERES NESTA FOLHA. PREVER SOBRETUDO ESPAÇOS PARA DR E DPS CONFORMEDETALHADO NO DIAGRAMA MULTIFILAR.
07- NO QUADRO DEVERÁ SER FIXADO, ATRAVÉS DE DISPOSITIVO PRÓPRIO, O SEU DIAGRAMA, CONTENDO
TODAS AS PROTEÇÕES ENVOLVIDAS CONFORME EXECUTADO .
08- AS TERMINAÇÕES DOS ELETRODUTOS NO QUADRO ELÉTRICO DEVERÃO SER COM CONECTOR TIPO
BOX RETO, COM BUCHA E ARRUELA DE ACABAMENTO, ADEQUADAS ÀS BITOLAS DO MESMO. AS
ELETROCALHAS DEVERÃO SER PROVIDAS DE FLANGES PRÉ-MOLDADOS CONFORME DIMENSÕES DEPROJETO.
09- AS TERMINAÇÕES DOS CABOS NO QUADRO ELÉTRICO DEVERÃO RECEBER TEMINAL DO TIPO AGULHAPARA CONEXÃO COM OS BORNES DOS DISJUNTORES E TERMINAL TIPO OLHAL PARA CONEXÃO AOS
BARRAMENTOS. TODOS OS TERMINAIS DEVERÃO SER COMPRIMIDOS ATRAVÉS DE FERRAMENTAADEQUADA.
10- O QUADRO DEVERÁ ESTAR LIMPO, LIVRE DE ARGAMASSAS, POEIRA, CAPA DE CABOS, FILAMENTOS DE
CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À INSTALAÇÃO.
11- OS TERMINAIS DAS BARRAS DE CONEXÃO NÃO UTILIZADOS DEVERÃO SER ISOLADOS POR CAPAPROTETORA ADEQUADA, DO MESMO FABRICANTE DAS BARRAS DE CONEXÃO .
12- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE COBRE COM
ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA 70 ºC 750V. DEVERÃO
SOBRETUDO, RECEBER ETIQUETAS DE IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO
A QUE ESTÁ LIGADO, CONFORME DESCRIÇÃO DO CAMPO "CIRCUITO" DO QUADRO DE CARGASCORRESPONDENTE.
13 - ATERRAR TODAS AS PORTAS DOS QUADROS ATRAVÉS DE CABO DE COBRE #6,0mm² ISOLAÇÃO VERDEEM PVC 70°C 750V.
INTERRUPTOR DIFERENCIAL RESIDUAL (IDR). CARACTERÍSTICAS
TÉCNICAS:- TIPO AC;
- CORRENTE NOMINAL (In): CONFORME INDICAÇÃO;
- SENSIBILIDADE: 30mA; TENSÃO MÁXIMA: 415Vca TETRAPOLAR;
FREQUÊNCIA: 60Hz.
SIMBOLOGIA P/ QUADRO:
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃOHALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,CLASSE 5 DE ENCORDOAMENTO (FASES - COR PRETA).
DISPOSITIVO PROTETOR DE SURTOS (DPS) PARA FASES.
CARACTERÍSTICAS TÉCNICAS DOS DPS's CLASSE I E CLASSE II,SEGUNDO NBR5410:
- OBEDECER A NBR IEC 61.643-1; Up (NÍVEL DE PROTEÇÃO):INFERIOR A 1,5kV;
- Uc (MÁXIMA TENSÃO DE OPERAÇÃO CONTÍNUA): 175V;- Iimp (CORRENTE DE IMPULSO): SUPERIOR A 12,5kA (10/350us);
- In (CORRENTE NOMINAL DE DESCARGA): SUPERIOR A 20kA
(8/20us) PARA REDES TRIFÁSICAS;
UTILIZAR NAS FASES COMO PROTEÇÃO BACKUP, FUSÍVEISMODULARES NH-63A gG/gL.
DISJUNTORES TERMO-MAGNÉTICOS (MINI DISJUNTORES),CURVAS B, C OU D CONFORME INDICAÇÃO NOS QUADROS,SEGUNDO A NORMA IEC-60947-2 E DIMENSIONADOS PARA
Icc = 5,0kA/220V( MONOPOLAR, BIPOLAR E TRIPOLAR,
RESPECTIVAMENTE).
DISJUNTOR GERAL:
- TIPO EM CAIXA MOLDADA, TERMOMAGNÉTICO E
DIMENSIONADOS PARA Icc MÍNIMO = 10,0kA/220V.
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃOHALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,CLASSE 5 DE ENCORDOAMENTO (NEUTRO - COR AZUL CLARO).
CABO DE COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃOHALOGENADO E COM BAIXA EMISSÃO DE FUMAÇA, 70°C 750V,CLASSE 5 DE ENCORDOAMENTO (TERRA - COR VERDE).
NOTAS GERAIS DOS QUADROS:
1- QUANDO UM DISJUNTOR OU FUSÍVEL ATUA, DESLIGANDO ALGUM CIRCUITO OU A
INSTALAÇÃO INTEIRA, A CAUSA PODE SER UMA SOBRECARGA OU UM CURTO-CIRCUITO.
DESLIGAMENTOS FREQUENTES SÃO SINAL DE SOBRECARGA. POR ISSO, NUNCA TROQUE
SEUS DISJUNTORES OU FUSÍVEIS POR OUTRO DE MAIOR CORRENTE (MAIOR AMPERAGEM)
SIMPLESMENTE. COMO REGRA, A TROCA DE UM DISJUNTOR OU FUSÍVEL POR OUTRO DE
MAIOR CORRENTE REQUER, ANTES, A TROCA DOS FIOS E CABOS ELÉTRICOS, POR OUTROS
DE MAIOR SEÇÃO (BITOLA).
2- DA MESMA FORMA, NUNCA DESATIVE OU REMOVA A CHAVE AUTOMÁTICA DE PROTEÇÃOCONTRA CHOQUES ELÉTRICOS (DISPOSITIVOS DR), MESMO EM CASO DE DESLIGAMENTOSSEM CAUSA APARENTE. SE OS DESLIGAMENTOS FOREM FREQUENTES E, PRINCIPALMENTE,
SE AS TENTATIVAS DE RELIGAR A CHAVE NÃO TIVEREM ÊXITO, ISSO SIGNIFICA, MUITO
PROVAVELMENTE, QUE A INSTALAÇÃO ELÉTRICA APRESENTA ANOMALIAS INTERNAS, QUE
SÓ PODEM SER IDENTIFICADAS E CORRIGIDAS POR PROFISSIONAIS QUALIFICADOS. A
DESATIVAÇÃO OU REMOÇÃO DA CHAVE SIGNIFICA A ELIMINAÇÃO DE MEDIDA PROTETORA
CONTRA CHOQUES ELÉTRICOS E RISCO DE VIDA PARA OS USUÁRIOS DA INSTALAÇÃO.
DETALHE DA ADVERTÊNCIA SEGUNDO A NBR 5410A SER FIXADA NO INTERIOR DO QUADRO ELÉTRICO
ADVERTÊNCIA
ATÉ 6 2
7 A 12 3
13 A 30 4
N>30 0,15xN
QUANTIDADE DE CIRCUITOS EFETIVAMENTE DISPONÍVEL
N
ESPAÇO MÍNIMO DESTINADO A RESERVA (EM NÚMEROS DE
CIRCUITOS)
TABELA 1: ESPAÇO RESERVA
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDESUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDEPROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
FOLHA:
04
05
ETAPA:
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVODIAGRAMA MULTIFILAR
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL VIABILE00 27/09/2012
DATAOBJETOREVISÃO
DATA:
NOME DO ARQUIVO CAD:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
UNIDADE:ESCALA:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-04-PE-T1T.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
TIPO T1T - TÉRREA
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE02 29/10/2012
REVISÃO DA ARQUITETURA VIABILE01 18/10/2012
SUBSECRETARIA DE INOVAÇÃO E LOGISTICASUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
Secretaria de Estado de Saúde de Minas GeraisCidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
EMISSÃO FINAL VIABILE03 08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE04 01/02/2013
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS VIABILE05 17/09/2013
5-OS COMPONENTES E MATERIAIS ESPECIFICADOS NESTE PROJETO SÃO REFERÊNCIAS E PODERÃO SER SUBSTITUÍDOSPOR EQUIVELENTES TÉCNICOS (APRESENTAR PROTÓTIPO PARA APROVAÇÃO POR PARTE DA FISCALIZAÇÃO DAS OBRAS).
CIRCUITO DESCRIÇÃO
16 23 32 25 50 85 170 510 850 1530
L1 4 - 34 - - - - - - -
L2 14 - 28 - - - - - - -
L3 - - 28 - - - - - - -
L4 ILUMINAÇÃO CIRCULAÇÃO E ESPERA 20 - 24 - - - - - - -
L5 ILUMINAÇÃO ÁREA EXTERNA - 23 - - - - - - - -
T1 TOMADAS SALA DE ESPERA - - - - - 6 - - - -
T2 TOMADAS RECEPÇÃO - - - - - - 4 - - -
T3 TOMADAS VACINAÇÃO - - - - - 1 - 1 - -
T4 TOMADAS VACINAÇÃO - - - - - - 2 1 - -
T5 TOMADAS TRIAGEM/ TOLETA - - - - - 3 4 - - -
T6 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 1 - - - - - 3 2 - - -
T7 TOMADAS ATENDIMENTO MULTIPROFISSIONAL 2 - - - - - 3 2 - - -
T8 TOMADAS SALA DE CURATIVOS - - - - - 3 - - - -
T9 TOMADAS SALA DE REUNIÃO - - - - - 4 - - - -
T10 TOMADAS SALA DE REUNIÃO - - - - - 2 - 1 - -
T11 TOMADA GELADEIRA SALA DE REUNIÃO - - - - - - - 1 - -
T12 TOMADA MICRO-ONDAS SALA DE REUNIÃO - - - - - - - - - 1
T13 - - - - 2 10 - - - -
T14 TOMADAS GINECOLOGIA - - - - - 4 2 - - -
T15 TOMADAS CUIDADOS BÁSICOS - - - - - 4 2 - - -
T16 PONTO DE FORÇA COMPRESSOR - - - - - - - - - -
T17 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - 6 - - - -
T18 TOMADAS CONSULTÓRIO ODONTOLÓGICO - - - - - - - 2 - -
T19 BLOCO AUTONOMO - - - 6 - - - - - -
T20 - - - - - 5 2 - - -
T21 TOMADAS AGENTES DE SAÚDE - - - - - 3 4 - - -
T22 - - - - - 10 - - - -
T23 PONTO DE FORÇA CHUVEIRO VESTIÁRIO MASCULINO – 220V - - - - - - - - - -
T24 PONTO DE FORÇA CHUVEIRO VESTIÁRIO FEMININO – 220V - - - - - - - - - -
T25 TOMADAS COPA - - - - - 4 - 1 - -
T26 TOMADA COPA – MICRO-ONDAS - - - - - - - - - 1
T27 TOMADAS DML/ RESÍDUOS/ PÁTIO DE ATIVIDADES - - - - - 4 - 1 - -
T28 PONTO DE FORÇA AR-CONDICIONADO VACINAÇÃO - - - - - - - - - -
T29 PONTO DE FORÇA AR-CONDICIONADO TRIAGEM - - - - - - - - - -
T30 PONTO DE FORÇA AR-CONDICIONADO COLETA - - - - - - - - - -
T31 - - - - - - - - - -
T32 - - - - - - - - - -
T33 TOMADAS CFTV - - - 5 - - - - - -
T34 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO - - - - - - - - - -
T35 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 1 - - - - - - - - - -
T36 PONTO DE FORÇA AR-CONDICIONADO CUIDADOS BÁSICOS 2 - - - - - - - - - -
T37 PONTO DE FORÇA AR-CONDICIONADO SALA DE CURATIVOS - - - - - - - - - -
T38 PONTO DE FORÇA AR-CONDICIONADO GINECOLOGIA - - - - - - - - - -
T39 PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 1 - - - - - - - - - -
T40 PONTO DE FORÇA AR-CONDICIONADO CONSULTÓRIO ODONTOLÓGICO 2 - - - - - - - - - -
T41 PONTO DE FORÇA AR-CONDICIONADO SALA DE REUNIÃO - - - - - - - - - -
T42 PONTO DE FORÇA AR-CONDICIONADO ESTERILIZAÇÃO - - - - - - - - - -
T43 - - - - - - - - - -
T44 PONTO DE FORÇA AR-CONDICIONADO AGENTES DE SAÚDE - - - - - - - - - -
T45 TOMADA ESTERELIZAÇÃO - AUTOCLAVE - - - - - - - - 1 -
T46 TOMADA RACK - - - - - - - - 1 -
T47 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - -
T48 PONTO DE FORÇA AR-CONDICIONADO ESPERA - - - - - - - - - -
T49 TOMADA RACK SONORIZAÇÃO - - - - - - - - 1 -
TOTAL 38,00 23,00 114,00 11,00 2,00 75,00 24,00 8,00 3,00 2,00
ILUMINAÇÃO (W)
BLOCO AUTONOMO
(W)
SINALIZAÇÃO(W)
TOMADAS (W)
ILUMINAÇÃO CUIDADOS BÁSICOS URG. E EMERG., ATEND. MULTIPROFISSIONAL, COLETA, SALA DE REUNIÃO E EDUCAÇÃO, IS MASC. E FEM., CIRCULAÇÃO
ILUMINAÇÃO COMPRESSOR, IS, GINECOLOGIA, CONSULTÓRIO ODONTOLÓGICO, GUARDA MEDICAMENTOS, AGENTES DE SAÚDE, DEPÓSITO, APOIO AGENTES ENDEMIAS, SALA LAVAGEM E DESINF. MATERIAIS, ESTERILIZAÇÃO, ACESSO FUNCIONÁRIOS, DML E RESÍDUOS.
ILUMINAÇÃO RECEPÇÃO, VACINAÇÃO, TRIAGEM, SALA DE CURATIVOS, ÁREA COBERTA, ESCOVÁRIO, ALMOXARIFADO, VEST. MASC E FEM, COPA.
TOMADAS I.S./ SALA DE APOIO AGENTES ENDEMIAS/ CIRCULAÇÃO/ BEBEDOUROS
TOMADAS ESCOVÁRIO/ GUARDA MEDICAMENTOS/ ALMOXARIFADO/ DEPÓSITO
TOMADAS LAVAGEM E DESINFECÇÃO DE MATERIAIS/ ESTERILIZAÇÃO/ VESTIÁRIO MASC. E FEM.
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL 1
PONTO DE FORÇA AR-CONDICIONADO ATENDIMENTO MULTIPROFISSIONAL 2
PONTO DE FORÇA AR-CONDICIONADO LAVAGEM E DESINFECÇÃO DE MATERIAIS
F.P.POTÊNCIA TOTAL TENSÃO
FASESEQUILÍBRIO
PROTEÇÃO
InCURVA
6500 1110 850 (kVA) (V) R S T (A) (A) (m)
- - - 0,95 1,15 1,21 220 RS 0,61 0,61 0,00 5,51 16 C 4,0 48
- - - 0,95 1,12 1,18 220 TR 0,59 0,00 0,59 5,36 16 C 4,0 31
- - - 0,95 0,90 0,94 220 ST 0,00 0,47 0,47 4,29 16 C 4,0 54
- - - 0,95 1,09 1,15 220 RS 0,57 0,57 0,00 5,21 16 C 4,0 49
- - - 0,95 0,53 0,56 220 ST 0,00 0,28 0,28 2,53 16 C 2,5 51
- - - 0,85 0,51 0,60 127 R 0,60 0,00 0,00 4,72 16 C 4,0 47
- - - 0,85 0,68 0,80 127 S 0,00 0,80 0,00 6,30 16 C 4,0 42
- - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 44
- - - 0,85 0,85 1,00 127 R 1,00 0,00 0,00 7,87 16 C 4,0 44
- - - 0,85 0,94 1,10 127 S 0,00 1,10 0,00 8,66 16 C 4,0 40
- - - 0,85 0,60 0,70 127 T 0,00 0,00 0,70 5,51 16 C 4,0 37
- - - 0,85 0,60 0,70 127 R 0,70 0,00 0,00 5,51 16 C 4,0 32
- - - 0,85 0,26 0,30 127 R 0,30 0,00 0,00 2,36 16 C 2,5 32
- - - 0,85 0,34 0,40 127 T 0,00 0,00 0,40 3,15 16 C 4,0 40
- - - 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 16 C 4,0 41
- - - 0,85 0,51 0,60 127 S 0,00 0,60 0,00 4,72 16 C 4,0 41
- - - 0,85 1,53 1,80 127 T 0,00 0,00 1,80 14,17 16 C 6,0 41
- - - 0,85 0,95 1,12 127 R 1,12 0,00 0,00 8,80 16 C 4,0 48
- - - 0,85 0,68 0,80 127 R 0,80 0,00 0,00 6,30 16 C 4,0 32
- - - 0,85 0,68 0,80 127 S 0,00 0,80 0,00 6,30 16 C 4,0 29
- - 1 0,85 0,85 1,00 220 ST 0,00 0,50 0,50 4,55 16 C 4,0 20
- - - 0,85 0,51 0,60 127 T 0,00 0,00 0,60 4,72 16 C 4,0 15
- - - 0,85 1,02 1,20 127 R 1,20 0,00 0,00 9,45 16 C 4,0 9
- - - 0,85 0,15 0,18 127 S 0,00 0,18 0,00 1,39 16 C 2,5 9
- - - 0,85 0,77 0,90 127 T 0,00 0,00 0,90 7,09 16 C 4,0 22
- - - 0,85 0,94 1,10 127 R 1,10 0,00 0,00 8,66 16 C 4,0 17
- - - 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 16 C 4,0 11
1 - - 1,00 6,50 6,50 220 RS 3,25 3,25 0,00 29,55 32 C 4,0 8
1 - - 1,00 6,50 6,50 220 ST 0,00 3,25 3,25 29,55 32 C 4,0 9
- - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 16
- - - 0,85 1,53 1,80 127 R 1,80 0,00 0,00 14,17 16 C 4,0 15
- - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 16
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 43
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 39
- 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 39
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 32
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 32
- - - 0,85 0,13 0,15 127 S 0,00 0,15 0,00 1,16 16 C 2,5 9
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 36
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 29
- 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 24
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 28
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 33
- 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 15
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 12
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 36
- 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 14
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 14
- 1 - 0,85 1,11 1,31 220 TR 0,65 0,00 0,65 5,94 16 C 4,0 14
- - - 0,85 0,85 1,00 127 S 0,00 1,00 0,00 7,87 16 C 4,0 10
- - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 40
- 1 - 0,85 1,11 1,31 220 RS 0,65 0,65 0,00 5,94 16 C 4,0 36
- 1 - 0,85 1,11 1,31 220 ST 0,00 0,65 0,65 5,94 16 C 4,0 36
- - - 0,85 0,85 1,00 127 T 0,00 0,00 1,00 7,87 16 C 4,0 40
2,00 18,00 1,00 0,89 56,07 63,07 220 RST 22,27 21,08 19,72 165,72 200 D - -
CHUVEIROS (W)
AR CONDICIONADO
(W)
COMPRESSOR (W)
CORRENTE NOMINAL
CONDUTOR (mm²)
COMPRIMENTO MÁXIMO DO
CIRCUITO
(kW)
LIMITE:
3,00%
1,03%
0,65%
0,90%
1,00%
0,81%
1,50%
1,79%
1,64%
2,35%
2,35%
1,38%
1,19%
0,82%
0,85%
1,75%
1,31%
2,62%
2,86%
1,36%
1,24%
0,36%
0,48%
0,58%
0,14%
1,06%
1,00%
0,59%
0,92%
1,04%
0,85%
1,44%
0,85%
1,00%
0,90%
0,90%
0,74%
0,74%
0,11%
0,84%
0,67%
0,56%
0,65%
0,77%
0,35%
0,28%
0,84%
0,32%
0,32%
0,32%
0,53%
2,13%
0,84%
0,84%
2,13%
-
QUEDA DETENSÃO EFETIVA
QDC-T1T-RELAÇÃO DE CARGAS E MEMÓRIA DE CÁLCULO MEMÓRIA DE CÁLCULOQUEDA DE TENSÃO
FOLHA:
05
05
ETAPA:
INSTALAÇÕES ELÉTRICAS
PROJETO EXECUTIVOQUADRO DE CARGAS
VÁRIAS UNIDADES NO ESTADO DE MINAS GERAIS
Av. Augusto de Lima, nº655conj. 418 - Centro - BH
Telefax: (31) 3324-2702
http://www.viabile.com.br
viabile@viabile.com.br
VERIFICAÇÃO
EMISSÃO INICIAL VIABILE00 27/09/2012
DATAOBJETOREVISÃO
DATA:
NOME DO ARQUIVO CAD:
DESENVOLVIMENTO:
BRENO ASSIS DE OLIVEIRA SETEMBRO/2013
UNIDADE:ESCALA:
INDICADA MILÍMETROS
CREA: 78.667/D
RESPONSÁVEL TÉCNICO:
BRENO ASSIS DE OLIVEIRA
PROPRIETÁRIO:
SECRETARIA DO ESTADO DE SAÚDE DE MINAS GERAIS
460-UBSSS-R05-ELE-05-PE-T1T.DWG
UBS MINAS - PROJETO MODELO
DISCIPLINA:
PROJETO:
ENDEREÇO:
CONTEÚDO:
GERENCIAMENTO E PROJETO:
3-CONFERIR MEDIDAS NO LOCAL.
2-DIREITOS AUTORAIS RESERVADOS - LEI FEDERAL 9.610 DE 19/02/1996.
1-PROIBIDA REPRODUÇÃO OU ALTERAÇÃO DO CONTEÚDO SEM AUTORIZAÇÃO DOS RESPONSÁVEIS TÉCNICOS DO PROJETO.
NOTAS:
4-COTAS EM CENTÍMETROS.
SUBSECRETARIA DE VIGILÂNCIA E PROTEÇÃO Á SAÚDESUPERINTENDÊNCIA DE VIGILÂNCIA SANITÁRIA
DIRETORIA DE INFRAESTRUTURA FÍSICA
PROJETO MODELO UNIDADE BÁSICA DE SAÚDEPROJETO DE ACORDO COM RDC-50/2002 E
É DE RESPONSABILIDADE DO MUNICIPIO APROVAÇÃO COM A IMPLANTAÇÃO NO TERRENO ESCOLHIDO.
RESOLUÇÃO 1797/09 DA SES-MG
TIPO T1T - TÉRREA
REVISÃO DA ARQUITETURA VIABILE01 18/10/2012
ALIMENTAÇÃO DOS PONTOS DE CFTV, RACK DE SONORIZAÇÃO E BEBEDOUROS VIABILE02 29/10/2012
SUBSECRETARIA DE INOVAÇÃO E LOGISTICASUPERINTENDENCIA DE GESTÃO
DIRETORIA DE GESTÃO DA REDE FÍSICA
Secretaria de Estado de Saúde de Minas GeraisCidade Administrativa Presidente Tancredo Neves
Rodovia Pref. Américo Gianetti s/nº - Bairro: Serra Verde - B. Hte -Minas Gerais - CEP: 31630-900 SES-MG Predio Minas - 12º e 13º andar
EMISSÃO FINAL VIABILE03 08/11/2012
ADEQUAÇÃO DA ARQUITETURA CONFORME VISA VIABILE04 01/02/2013
FORMATO INTERNACIONAL A1 (841 x 594mm)
abrasip-mg
READEQUAÇÃO DA ARQUITETURA E COMENTÁRIOS VIABILE05 17/09/2013